Supply and Installation of Hot water Generator for Vapour absorption Chiller

Specification for Supply and Installation of Hot water Generator for Vapour absorption Chiller  Heat Output                           :  50000 kCal/hType                                       :  Horizontal firingNo.of passes                           :  3Fuel                                        :  LPG firedWater Pump flow rate            :  2.9 m3/hOutlet Temperature                :  94 – 96 0CTemp. difference   ( delta T)  : 13 - 18 0CEfficiency                               :   >90 %Chimney:               Material                   :    MS               Dia                           :   150 mm                Height                      :   3 mFuel                                        :  LPGNo. of gas line                        :  6  Inclusions:1.     Unloading ,erection of Hot water generator and accessories2.     Metal foundation for Hot water generator and other accessories3.     Gas  pipeline up to the inlet of the unit4.     Chimney and flue gas duct between main unit and chimney5.     Prewired-Control panel with necessary instruments Note: System should be compatible to vapour absorption Chiller (Cooling Capacity 3.3 TR, hot water Inlet & Outlet temperatures 95 and 90 0C, Flow rate 2.9 m3/h, DN 40)

Reference: 
MEE/12-13/303/DSTX/KSRS/VII
Opening Date: 
29/10/15
Closing Date: 
19/11/15
Address: 
Dr. K SRINIVAS REDDY PROFESSOR ROOM NO : 204 HEAT TRANSFER AND THERMAL POWER LABORATORY DEPARTMENT OF MECHANICAL ENGINEERING IIT MADRAS,CHENNAI-600036
URL for tenderwizard site: 
http://tenders.iitm.ac.in/?q=open-tenders